Overview Product Description Vertical Double Bank Louver VDL150-3 Rainwater Penetration Coefficient of Entry Tested by B
Basic Info
Model NO. | Togen |
Specification | louver height: 1055mm |
Trademark | Togen |
Origin | China |
HS Code | 73089000 |
Production Capacity | 4500 Meter/Meters Per Day |
Product Description
Product DescriptionVertical Double Bank Louver VDL150-3
Blade Pack Depth | 145mm |
Frame Depth | 150mm |
Pitch | 75mm |
Visual Impact | Hidden |
Free Area | / |
Rainwater Penetration
VENTILATION RATE | WATER FLOW RATES | Effectiveness | Class | ||
Volume m³/s | Velocity m/s | Supply l/h | Penetrated l/h | ||
0.00 | 0.00 | 97.2 | 0 | 100% | A |
0.46 | 0.50 | 97.2 | 0 | 100% | A |
0.93 | 1.00 | 97.2 | 0 | 100% | A |
1.39 | 1.50 | 97.2 | 0 | 100% | A |
1.86 | 2.00 | 97.2 | 0 | 100% | A |
2.32 | 2.50 | 97.2 | 0 | 100% | A |
2.79 | 3.00 | 97.2 | 0 | 100% | A |
3.26 | 3.50 | 97.2 | 0 | 100% | A |
Coefficient of Entry
loure face velocity | air flow rate | |||
louver pd Pascals | m/s | test m³/s | theoretical m³/s | coefficient Ce |
10.3 | 1.10 | 1.026 | 3.836 | 0.268 |
24.2 | 1.72 | 1.596 | 5.881 | 0.271 |
37.5 | 2.17 | 2.022 | 7.320 | 0.276 |
52.7 | 2.57 | 2.395 | 8.678 | 0.276 |
66.2 | 2.90 | 2.693 | 9.726 | 0.277 |
79.9 | 3.20 | 2.973 | 10.685 | 0.278 |
95.4 | 3.47 | 3.232 | 11.676 | 0.277 |
112.0 | 3.72 | 3.459 | 12.651 | 0.273 |
130.0 | 4.01 | 3.735 | 13.630 | 0.274 |
143.0 | 4.27 | 3.969 | 14.295 | 0.278 |
mean Ce | 0.275 | |||
Class | 3 |
Tested by BSRIA-EN-13030:2001Design
DesignOur performance louver systems are designed using airflow simulation by CFD(computational fluid dynamics)software to get the best balance between airflow and rain defense performance
TestingTesting
Weather Louvre: UK BSRIA/US AMCA Testing
The industry standard for weather testing of Louver in the UK was developed by BSRIA(Building Services Research & Information Association) and HEVAC adopted in 2001 as a British & European Standard: BS EN 13030:2001. The principles of EN 13030 are replicated in the USA under the AMCA Standard 500-L, "Laboratory Methods of Testing Louvers for Rating"All of our louver systems have been tested either by BSRIA or by AMCATwo key performance areas:1. Rain Defence ClassificationThe ability to prevent rainwater from penetrating the louverClass | Effectiveness | Max. allowed rain penetration l/h/m² |
1 | 1 to 0.99 | 0.75 |
2 | 0.989 to 0.95 | 3.75 |
3 | 0.949 to 0.80 | 15.00 |
4 | Below 0.80 | Greater than 15.00 |
Class | Airflow Effectiveness | Performance Rating |
1 | 0.4 to 1 | Excellent |
2 | 0.3 to 0.399 | Very Good |
3 | 0.2 to 0.299 | Good |
4 | 0.199 & below | Fair |
If you are interested in our product or have any questions. Please feel free to contact us!
Bird Mesh ScreenNotes:
W--Width of the mesh
D--Diameter of the wire
Regular Size of Insect/Bird Mesh Screen(mm) | ||
Mesh | Width of the mesh | Diameter of the wire |
Insect Mesh Screen | 1.5*1.5 | 0.25 |
2*2 | 0.5 | |
2.5*2.5 | 0.5 | |
Bird Mesh Screen | 5*5 | 0.8 |
10*10 | 1,1.6 | |
11.2*11.2 | 1.6 | |
12.5*12.5 | 1.6 |
S--SWD
L--LWD
T--Strand thickness
Bird Mesh Screen(Diamond) | ||
Mesh | Width of the mesh | Stand thickness |
Bird Mesh Screen(Diameter) | 10*20 | 1,1.5 |
20*40 | 1,1.5 |